  1. Mopar71

    Amines in boiler water

    Thats a good point,where I use to work we had a small condenser on the deaeator to condense a sample so we could check the amount of sodium sulfite in the deaerator. I will talk to the manager and the chemical company and see if this can be done.Thanks
  2. Mopar71

    Amines in boiler water

    Ok, I got it, so the condensate sample would have to be taken closer to the steam source like a drip leg.The air handler has a humidifier that injects steam in to the occupied space to raise humidity.In the winter months more so because of the drier winter air.In the summer the air is much more...
  3. Mopar71

    Amines in boiler water

    Here is the problem in more detail,amines are being added to the boiler with a metering pump set at a specific dose.The problem is that the amines are being detected in the ocupied space,people complaining of smell and iritation.they currently check PH of condensate return.thats how they...
  4. Mopar71

    NON RETURN VALVE LEAKING

    If I am not mistaken,there should be a drain valve at the bottom of the non return valve,this is used to bleed any accumulating condensate.we used to open it at startup of the boiler till it reached full pressure then shut it. also at shutdown open it and leave it open.
  5. Mopar71

    Amines in boiler water

    I dont know if this is the right forum for this but I need to know if there is a way to check amines in the steam supply going out to the plant?