  1. Aggie1998

    dedicated power for boiler

    I work with the Army Corps of Engineers and this is a Battalion Headquarters building. The electrical contractor was arguing with me that adding a few receptacles to the circuit would not hurt anything. The manufacturers recommendation was enough to make him do it the right way but I wanted to...
  2. Aggie1998

    dedicated power for boiler

    Thanks for the info. I have a certified electrician installing the power for the boiler. I was just wondering the why. The boiler manufacturer installation guide clearly states that is has to be a dedicated conduit, circuit, neutral, etc.
  3. Aggie1998

    dedicated power for boiler

    I have a boiler that is to be installed and the drawings calls for a dedicated circuit, conduit,etc. on a 20 amp breaker. The boiler is only pulling 5 amps. Why can't I put anything else in the conduit and on this circuit?