  1. deeveeyes

    DG set and non-linear loads

    busbar,you have mentioned some site. I am not able to locate it. Please give url of the site.
  2. deeveeyes

    DG set and non-linear loads

    I am told that when a DG set is feeding non-linear loads with high distortion levels its loading or rating needs to be derated. Can somebody advise me how to calculate the derating factor, if THD(I) and THD(v) levels are known. What is the effect of Harmonics on DG set ? ARe there any articles...
  3. deeveeyes

    Input Power to Computers

    jbartos, for xl > xc at 36 uF, the value of L is 281.7 mH and not 28.17 mH as indicated by you earlier. This is not workable. Hence there is no alternative than to use LC combination tuned to near 150 Hz, but we have to live with leading PF at the output of filter, hence pls advice what other...
  4. deeveeyes

    Input Power to Computers

    Jbartos, This will tune it to 158 Hz and will amplify 3rd harmonic instead of reducing it ?! I want to tune it to less than 150 Hz. !!
  5. deeveeyes

    Input Power to Computers

    Thanks Jbartos: The LC combination is tuned near 3rd harmonic and hence how can I make it lagging ?? for ex: 36 uF and 32mH will tune to 3rd (on 50 Hz supply) and combination will be having a Leading PF!
  6. deeveeyes

    Input Power to Computers

    We are working on design of a filter to filter out 3rd harmonics generated by SMPS of computers. However, when we conducted a log on the input parameters of a computer, we found that it draws around 0.6 Amps @ 0.6 PF lead !! The filter itself is a passive filter (LC combination) and hence would...
  7. deeveeyes

    harmonic rejection filtering

    Thanks PEEBEE and ELECTRICPETE. Can someone tell me the configuration for a low pass filter ?? I thought tank circuit as envisaged by me acts effectively to reject 3rd harmonic, but the problem is to design the components to carry high currents. Is there any way to overcome this problem ??
  8. deeveeyes

    harmonic rejection filtering

    I am working on a design of harmonic rejection filter to reject 3rd harmonics present in neutral. I plan to use a capacitor of 120 uF and inductor of around 9 mH in parallel connection. The analysis shows that this combination has high impedance at 3rd harmonic (150 Hz)but the programme also...
  9. deeveeyes

    Harmonic amplification with Turbogenerator supply

    In one of the cement plant where we conducted harmonic audit we found that on the HT 6.6. KV BUS, the Voltage as well as current distortion drastically increased when the supply was switched from Utility supply to their own Captive Turbogenerator supply. It increased from nearly 2% to almost...
  10. deeveeyes

    Energy consumption reduction in glass melting furnace

    We have a glass melting furnace 50 KW fed by a furnace transformer,cycloconverter and an uncontrolled rectifier, feeding the furnace at 11V DC. One of the Energy auditors measured the energy consumption at the input of furnace and found that 223 KWH energy was used to melt only around 3.4 Kgs of...
  11. deeveeyes

    Effect of Non-linear loads on DG SET

    WE HAVE COME ACROSS A CASE, WHERE A 1250 KVA, 415V DG SET IS NOT ABLE TO TAKE THE LOAD OF 2 DC DRIVES EACH RATED AT 500 KVA. WE HAVE BEEN TOLD BY DG SET MANUFACTURER THAT IT IS DUE TO HARMONICS PRODUCED BY DC DRIVES. THE DG SET IS 415V AND SUPPLY TO DC DRIVES DIRECTLY WITHOUT ANY TRANSFORMER IN...
  12. deeveeyes

    HARMONIC FILTER ACROSS DC DRIVE

    Thanks jbartos. where can I access the reference article of Ashmore s.
  13. deeveeyes

    HARMONIC FILTER ACROSS DC DRIVE

    wE PLAN TO CONNECT A HARMONIC FILTER TUNED TO 4.7TH ACROSS OUR DC DRIVE 250 KW. WILL THERE BE ANY EFFECT ON THE WORKING OF DC DRIVE ? THE DRIVE HAS A DEDICATED TRANSFORMER AND THE FILTER IS PROPOSED TO BE INSTALLED PARALLEL TO THE DRIVE ?
  14. deeveeyes

    HARMONIC FILTERS & PF IMPROVEMENT CAPACITORS

    Thanks everyone for lucid explanation. The filter manufacturer has again reverted to us telling that as long as the total quantum of capacitors being switched in along with the motors is below 8 - 10% of Proposed Filter Bank capacity, he does not foresee any problem in meeting IEEE limits of...
  15. deeveeyes

    HARMONIC FILTERS & PF IMPROVEMENT CAPACITORS

    I have a Power Control Centre (415V), from which a feeder feeds around 500 kw of load of Variable speed drives (6-pulse). Another feeder from this PCC feeds a Motor Control centre having 300 KW load. To improve the PF of motors, capacitors are connected across the motors directly. We are...
  16. deeveeyes

    HOW DO YOU CALCULATE SHORT CIRCUIT LEVEL ON A LOW TENSION BUS ?

    how does one calculate the short circuit level on a Low Tension bus when both utility and Captive Power (Diesel Genset) is connected to the same bus.&nbsp;&nbsp;There are all the three possibilities of operation: Utility only, Captive Power only and both utility + captive Power. <br><br>I need...
  17. deeveeyes

    How to determine what type of harmonic flitering to use?

    Unless the drive loads are varying throughout the load cycle, passive filters across the loads should give good results. One needs to understand the level of harmonics by actually measuring the harmonics and then decide if the harmonics are really harmful or can stay. PF can be improved on HT...