Hi all,
I am unable to get through with the calculation of undistributed soil temperature at different depth for Indian climatic conditions.
I have been referring to equation 4.9 in District Cooling Guide (Ashrae) cross referring weather data for Tmax, tlag, climatic constant etc. If anyone...
My response was on dewpoint based on your recorded reading where you didn't mention anything on pipe temp.
However if you think there are gaps in the insulation then suggest this should be rectified and then observed. Also you need to check the thickness of the insulation based on your heat...
How can there be a condensation on the surface of insulation which shows dew point of 25 & 20 Deg C. Whereas the space temperature has dew point of 14 Deg C . You need to check again with the Infrared sensor if the readings taken are correct.
Now I presume that the system what you are referring...
Hi all,
I am unable to get through with the calculation of undistributed soil temperature at different depth for Indian climatic conditions.
I have been referring to equation 4.9 in District Cooling Guide (Ashrae). If anyone has done please let me know with an example for any location...