  1. sbarkah

    Connection winding salient pole of AC generator to rotating rectifier

    Dear Mike, Well noted. We will do insulation test on the main rotor also, especially PI to ensure the condition based on insulation class. CMIIW. Thank you. Best Regards, Barkah
  2. sbarkah

    Connection winding salient pole of AC generator to rotating rectifier

    Dear Mike and Bill, Thank you for your respond. Actually, we have not any testing yet after replace suppressor and rewinding the rotor exciter. As both of you mentioned, before the alternator put back in service, we need to do as follows: 1. Flash the exciter to ensure exciter has enough...
  3. sbarkah

    Calling catserveng

    Dear Bill and Catserveng, Below LINK is our discussion as Bill's mentioned. http://www.eng-tips.com/viewthread.cfm?qid=358937 Thank in advance. BR, Barkah
  4. sbarkah

    Connection winding salient pole of AC generator to rotating rectifier

    Dear Bill. Appreciate with your respond. You are correct that the connection from rotating rectifier is not our issue as we didn't disassemble the connection of the rotating rectifier. We disconnected two leads of the main field from (-) and (+) terminal of the rotating rectifier, but...
  5. sbarkah

    Connection winding salient pole of AC generator to rotating rectifier

    Dear All, Attached is the lead that we discuss it...whether it may be connected to rotating rectifier with consider polarity or not. Thank you. BR, Barkahhttp://files.engineering.com/getfile.aspx?folder=4e6ef1d1-ddd2-4420-93e2-2e0b74de87db&file=PLTD-ROTOR-1.jpg
  6. sbarkah

    Connection winding salient pole of AC generator to rotating rectifier

    Dear All, Attached is our installed AVR. Thank you. BR, Barkahhttp://files.engineering.com/getfile.aspx?folder=031992aa-dcd8-496c-b3cf-3696c0a4b27a&file=A_ôMARK_Iö.jpg
  7. sbarkah

    Connection winding salient pole of AC generator to rotating rectifier

    Attachment-7 (last) Many thanks, Best Regards, Barkahhttp://files.engineering.com/getfile.aspx?folder=dcd41635-9601-4559-a7b6-3c3802b62a1b&file=Wiring_12_terminal_generator_MJB-355_to_AVR-.png
  8. sbarkah

    Connection winding salient pole of AC generator to rotating rectifier

    Attachment-6http://files.engineering.com/getfile.aspx?folder=94afca60-8299-469f-85bf-49fd4e031e0e&file=5.2._Instruction_for_MANUAL_control_of_Generators_MJB-355.png
  9. sbarkah

    Connection winding salient pole of AC generator to rotating rectifier

    Attachment-5http://files.engineering.com/getfile.aspx?folder=008e95d6-1f90-4c3a-bcb1-f4d17ab31fbe&file=MJB-355_leads_from_rotor_to_rotating_rectifier.png
  10. sbarkah

    Connection winding salient pole of AC generator to rotating rectifier

    Attachment-4http://files.engineering.com/getfile.aspx?folder=8e945a01-05dd-43a2-8028-4a38697564fe&file=Previous_and_current_condition_of_the_exciter.png
  11. sbarkah

    Connection winding salient pole of AC generator to rotating rectifier

    Attachment-3http://files.engineering.com/getfile.aspx?folder=4e44dea5-e1a9-44bc-a97b-bd10315648bd&file=Rotating_Rectifier_MJB-355.png
  12. sbarkah

    Connection winding salient pole of AC generator to rotating rectifier

    Attachment-2http://files.engineering.com/getfile.aspx?folder=8e736a95-6548-4bb3-80ec-b0cbda3c0723&file=Schematic_generator_rotor_and_exciter_rotor.png
  13. sbarkah

    Connection winding salient pole of AC generator to rotating rectifier

    Dear Bill and all members, I've tried upload some attachments relates to the thread. I hope it does work correctly. Thank you. Best Regards, Barkah...
  14. sbarkah

    Connection winding salient pole of AC generator to rotating rectifier

    Dear Bill, Well noted. From your explanation, I assume that we can connect both leads to rotating rectifier terminals (-) and (+) with no risk i.e. burns exciter, suppressor diode or rotating rectifier. And if wrong connection only has consequences the output voltage will no build up. Correct...
  15. sbarkah

    Connection winding salient pole of AC generator to rotating rectifier

    Dear Bill, Our AVR type is Marelli M40FA640A/A “MARK I”. LINK below is the manual of Marelli Generator and our generator type is MJB 355 MA 4B http://www.mase.no/cart/images/File/Bruksannvisninger-GB/SIN.UM.018.3.pdf http://www.mase.no/cart/images/File/Bruksannvisninger-GB/SIN.UM.018.3.pdf
  16. sbarkah

    Connection winding salient pole of AC generator to rotating rectifier

    Dear Bill, Thanks for your response. Yes, these are the leads of salient poles rotor which should connected to rotating rectifier. The KVA alternator is 680 kVA and output voltage is 400 VAC. We are worry to reconnect the lead since we didn't tag the (-) and (+) on these leads before...
  17. sbarkah

    Connection winding salient pole of AC generator to rotating rectifier

    Dear members, I have problem on our AC generator (Marelli Generator MJB 355) with salient pole rotor (4 poles). The AC generator was need to repair due to suspressor diode was broken, then we taken out the rotor to repair rotor exciter. We disconnected cables rotor's winding from rotating...