  1. RJC2008

    120/208VAC panel main breaker size

    Thanks for the response. In step 2, I am not clear on why you are adding 40 and 40? and where does the factor .866 come from? Could I not just take the sum of the VAs for the heaviest loaded phase and divide it by 120?
  2. RJC2008

    120/208VAC panel main breaker size

    I understand the concern and normally this would be a non-issue as I would size the breaker and feeder for the panel but this is truly special case. I need to know the absolute minimum sizes for both the breaker and feeder. The problem is that I am unsure of the calculation because the loads...
  3. RJC2008

    120/208VAC panel main breaker size

    Normally I would size the main breaker based on the panel rating. But, this panel does not need provisions for future expansion and all circuits are used I would like to have the smallest feeder possible and also the smallest circuit breaker possible.
  4. RJC2008

    120/208VAC panel main breaker size

    Hello, I have a 120/208 Vac panel that is fully populated and due to the nature of this panel installation there is not a need to provide additional expansion. The load is a mix of 120 and 208 lighting loads and receptacle loads (no motors etc.) The total load on the panel is 26,688VA. My...