my mistake. There is a differance between no load and load.
the no load readings are as follows
no load amps
A 17.45
B 13.49
C 13.50
under load Amps
A 17.62
B 13.08
C 13.84
After monitoring today the voltage does not vary more then 1 volt during 4 hours of run time
Amp loads vary less then...
Sorry it took so long to get back.. It's along way from anywhere so it took me time to get back to the machine.
The motor that failed was wired correctly (low voltage)
The Ph-Ph voltage readings are as follows:
Without load
Line A to B 250 volt
Line A to C 247 volt
Line B to C 242 volt
Under...
I've got a can crusher in the recycling industry with a 7 1/2 hP motor that has had 3 failures since we've put it in operation. This motor operates a blower that "typically" runs at close to full load motor amps.