Waross,
Thank you for your advise. I will run the generator governor in isochrous mode and short-cct the droop CTs on the AVR when I run the generator in islanding.
There are numbers of operation requirement;
- Utility only
- Utility with Inverter
- Utility with Generator
- Utility with Inverter and Generator
- Inverter only
- Inverter with Generator
The most difficult for me is the Inverter with Generator. What should I be carefull and take precustion...
Thanks all for the information.
In this project, there are three sources; Utility, Inverter( grid-tied type ) and generator. We are the generator supplier.
There is an intend to parallel all sources together.
I am planning to add; a synchronizer, a Load Shar Module ( LSM ) to provide droop and...
I have a project, need to parallel a generator set with an invertor output.
Generator; 20KW, 600V 3 Ph. 60Hz at 1800 rpm.
- Governor,Electronic always runs at constant speed 1800 rpm, no load to full load.
- Voltage regulator, Digital, self excited, constant output 600V, no load to full...
Hi All,
I have an application for a 3MW 4160V 3Ph. 60Hz generator to energize a 10MVA step up tranasformer 4.16/27.6 Kv.
Can it be done ? If it can, what caution I should be awared ?
Appreciated for advise and comment !