Thanks for the information. Pardon my basic questions...I'm an EE by training.
The Liebert rep is telling me I need a total of 10 Tons...because I am only considering sensible heat...not latent heat. Does this make sense to anyone?
I didn't consider the room/shell load..it seems to be...
Looking for advice on server room cooling sizing. I'm hoping to get some unbiased opinions from other pros who aren't trying to sell me something.
---
Part A:
We are moving 129 servers (4 racks), each with a nameplate rating of 350W, into a small room. Based on our measurements, each server...