Hi bacon4life,
The dry type air core reactor at this voltage level was not available in the past when the criteria for line connected reactor was implemented in the utility I work for. So when they appear nobody thought in using them until now, and not be me by the way, but I have to provide...
Hi Alan (Submonkey),
Each station (line end) will have a Y shunted solidly grounded reactor. Another utility is in charge of the remote end, so I don't know if the remote reactor will be air core or oil immersed type.
The line protection will be redundant distance with POTT (Permissive...
Hello 144X,
Options 1 and 2 provide useful information but only related to dry type air core reactors used in tertiaries of power transformers and not connected to Transmission Lines. However some of the criteria apply to both applications. There are some industry papers that offer more insight...
Hello,
We are installing a 30MVAR 230kV shunt air core dry type reactor to be connected to a Transmission Line for voltage control, and I am trying to determine protection requirements for the reactor. I have the following questions:
1) What kind of protection should be provided for shunt dry...