Just to clarify, I am not being asked if the panel can be refurbished. I agree that is an obvious no. Also, I didn't mean to give the impression that I wanted advice from "the internet yahoos" to use professionally. All I'm looking at is whether the incoming bus could be refurbished. I am no...
Thanks for the information. Just for grins, here's some pictures of what I'm dealing with. The site cleaned out the equipment before we arrived, so this is what we saw. Looks like the fire started in Section 5 (from the left). The bus enters at the top of Section 2. I have been told it's nothing...
I am working on a project to replace a motor control center that burned down. The client wants me to look into re-using the busbars feeding the MCC. The feeder busbars come from a sub-distribution panel nearby and enter through the top of the MCC. It doesn't look like the bars were above the...