i have inspected lots of motors with a thermal camera, the enviroment is the key factor i'd say, most problems are the air supply in the cooling fan, dirt build up on the cowlings restricting air supply to the windings, tends to get neglected through lack of maint. not sure on your question. but...
the vibration resonnance was 12 m/s at 1100rpm, what was also found that when motor was uncoupled from the drive it was showing 7 m/s at 1100rpm. 1100 seems to give the most vibration. having two motors going through 1 vsd is not common on our works.
not sure on exatct vib readings until i see him again tommorow. The virbration guy said the vibration frequencies were not consistant with each other, and not one set patteren was observed, the vibrations are variable depending in the speed you run the motors, at certain speeds you don't need a...
Hello,
Hope you can help! our contractor has recently installed 110 off new motors on our water treatment plant aeration lanes, they are 15kw on outside lanes and 11kw further along, they are drving a spash paddle through a gearbox, i think they are weg motors, flender box's, our vibration...