Continue to Site

Eng-Tips is the largest engineering community on the Internet

Intelligent Work Forums for Engineering Professionals

  • Congratulations KootK on being selected by the Eng-Tips community for having the most helpful posts in the forums last week. Way to Go!

Search results for query: *

  1. edison123

    Is an isolation transformer needed on a VFD input side?

    Update: Drive OEM informed a 690 V drive cannot be used for 415 V input because of capacitor charging capability. Their recommendation is a 3-winding D/D-Y isolation transformer with 30 deg phase shift for 12 pulse firing for harmonics reduction. Or go for an AC to AC drive eliminating all...
  2. edison123

    Is an isolation transformer needed on a VFD input side?

    Wye secondary with grounded neutral it is. I have an old 250 KVA trafo which I will rewind for 415 Delta and 690 V Wye with a 415 V tap.
  3. edison123

    Is an isolation transformer needed on a VFD input side?

    Thanks, gr8. So it would be a delta/wye transformer? Any reason why the VFD input should be a wye? Bill. Yes, I had the same idea. 415/690-415 trafo. Since the drive is 690 V rated, I guess there is a better safety factor (in terms of voltage) when it is used in 415 V?
  4. edison123

    Is an isolation transformer needed on a VFD input side?

    This week, we trialed a 125 KW VFD for testing LV motors in decoupled condition. During the trials, I noticed our LED lights started flickering even though they were switched off. When asked, the OEM drive guru said there will be harmonics fed into the system, and we need to install an...
  5. edison123

    Current clamp meter high voltage

    great info, System Protection and maparentau.
  6. edison123

    Motor VFD open loop no-load current is much higher than closed loop no-load current. Why?

    Thanks, Jeff. Forget PM synch motor, last week I asked to demo a 125 KW drive (reputed Japanese brand) for no-load testing of four normal cage motors with no-load currents varying from 90 to 250 Amps in my shop and the drive dealer team couldn't do it for any of them without the drive tripping...
  7. edison123

    Current clamp meter high voltage

    Their so-called manual has more disclaimers and caveats than actual usage info. I wouldn't touch it even with a 20 ft pole.
  8. edison123

    Current clamp meter high voltage

    I have a few Fluke and reputed Japanese make clamp meters of various current ratings. None of them is rated over 2000 V. Post more details and photos of your meter. As Bill asks, are you willing to risk your life with such a meter?
  9. edison123

    [Historic] Convert 25 Hz end of Frequency Changer to 60 Hz Synchronous Condenser

    Stator core of that era will be hot rolled silicon steel with higher loss than the later day low loss cold rolled steel. So, core was most likely changed. I doubt the 300 RPM rotor can withstand centrifugal forces at 720 RPM, so possible new rotor, bearings and bearing supports. Stator winding...
  10. edison123

    Impacts of loss of excitation on small hydro unit

    "The rest of section 7.6.5 indicates that some hydro units remain online without excitation for long enough to manually restore the excitation system." Manually intervene is the key point here. If your machine ran for 15 minutes with no operator action, better to check the rotor health.
  11. edison123

    Impacts of loss of excitation on small hydro unit

    IEEE 492 7.6.4 Asynchronous operation (field maintained) - (I have personally seen a 50 MW hydro machine completely destroyed in this operating condition) Operation of a generator out-of-synchronism with partial or full-field excitation maintained, places the most severe type of duty on the...
  12. edison123

    H1 H2 H3 wires for space heaters (Induction motor)

    OP said 4 x 240 V x 1000 W heaters with 3 terminals suitable either for 240 V or 120 V. If there is another connection possible for both 240 V and 120 V, please post here. Yes, 62.5 W for each heater and 250 W in total. Which is what I find in large motors. It's enough to keep the motor warm.
  13. edison123

    Motor VFD open loop no-load current is much higher than closed loop no-load current. Why?

    jpts - I don't have the voltages in open loop and closed loop, only the currents. iop - It's embedded round PM rotor.
  14. edison123

    Wound rotor motor with external brake option

    This is not an eddy current brake. It plain old fail-safe spring activated mechanical brake found in hoists.
  15. edison123

    Motor VFD open loop no-load current is much higher than closed loop no-load current. Why?

    V/Hz is set correctly in open loop. Drive is set for PM synch motor mode. In open loop, the motor had odd electromagnetic noises on top of high current. In closed loop, low current and smooth running. Guess, PM synch motors are odd beasts.
  16. edison123

    Wound rotor motor with external brake option

    The brake operates mechanically by springs in case of power loss/stop to hold the hoist in position. The DC supply releases the brake (by pulling in the springs) when the hoist is moving up/down. After seeing the excellent performance of my new 60 ton EOT crane which came with VFD's for...
  17. edison123

    Motor VFD open loop no-load current is much higher than closed loop no-load current. Why?

    Lionel - Yes, the custom designed drive is set for PM mode. Bill - The very idea of VFD is to have constant flux density V/Hz through the entire speed range.

Part and Inventory Search