  1. geordiejohn

    make existing single zone system multi zone

    Thank you SAK and Willard. The building is a big 2 storey open box which will be fitted out for call centre and cellular offices. There is an existing AHU which has space for a chilled water coil to be fitted. Most of the year will be predominantly a cooling load with small perimeter heating...
  2. geordiejohn

    make existing single zone system multi zone

    So say the system is in cooling mode supplying cool air to all rooms. An unoccupied perimeter room needs heating. The termofuser closes the damper reducing air into the room (say to 8 l/s per person). Then the heating requirement must be picked up by say perimeter heating with radiators. Then...
  3. geordiejohn

    make existing single zone system multi zone

    Thanks Compositepro I like the idea. I haven't seen them used here before. Trying to reuse the existing plant obviously cannot provide simultaneous heating and cooling in adjacent offices without another system...
  4. geordiejohn

    make existing single zone system multi zone

    Hello All - my first post. I'm looking at a large single zone mixing/recirc AHU with hot water coil and space for chilled water coil. This supplies a large open factory in Ireland. The factory is being converted into offices, several zones some small, some large. My first thought is to...