Eng-Tips is the largest engineering community on the Internet

Intelligent Work Forums for Engineering Professionals

Search results for query: *

  1. CPleasant

    FDC and Exterior Alarm

    I don't believe it is required. A.6.9.3.1 Audible alarms are normally located on the outside of the building. Listed electric gongs, bells, horns, or sirens inside the building, or a combination of such used inside and outside, are sometimes advisable. Outside alarms can be omitted where the...
  2. CPleasant

    Domes

    I've only come across domes in the residential systems I’ve designed, but I believe we use concealed pendents near the top of the dome. If there is a chance that the pipe may freeze, is there a way to make that area a dry pipe system?
  3. CPleasant

    Is learning Autosprink a waste of time?

    I went through the fire protection program at Seneca college and took both HydraCAD and AutoSprink. While I found that AutoSprink worked best for me. None of the companies I've worked for have used it. I'd say unless your working freelance you'll have to use the program the company you work for...
  4. CPleasant

    Finding min psi or gpm

    They don't want to change anything, but I did get it to work, they just can't store the tires higher then 5'-0 in that area.
  5. CPleasant

    Finding min psi or gpm

    Oh, and there are 8.0 K-factor heads, which makes the calc better, but still not good enough to work
  6. CPleasant

    Finding min psi or gpm

    I believe that since they are not changing the building or sprinkler system they don't need to upgrade the heads. The company just wants to know what they're ability to store the tires is, if any.
  7. CPleasant

    Finding min psi or gpm

    It's an existing system, they want to use it to store tires in without changing the sprinklers in the area
  8. CPleasant

    Finding min psi or gpm

    I am working on a project that requires the hydraulic calculation to have a 0.39/2600 density. I'm using HASS as my calc program and I can not input the density into the program. I need to get the minimum allowable end head condition in either psi or gpm. Heads are space 10x10 and are 5.6 k-factor.