Hi,
Is NEC considers plug-in rope light ( LEDs in clear tubing 50 ft long) as temporary installation?
Rope installed inside, above drop-in ceiling.
TIA
Quark,
Thank you for spending your time to explain all details of the process to me. I do not want spend any more of everybody’s time on the issue.
The answer is : To convert one gallon of liquid nitrogen to the gas at 70F and 100 psi takes 1235.5 Btus
Again, thanks to everybody who helped me...
Thanks to everybody for the inputs.
Warming the gas:
Q= 1.08 X CFM X (t1-t2)
1 gal of liquid nitrogen = 93.11 cubic feet
Q= 1.08 X 93.11 X (319+70) = 39117 Btu/gal of liquid or Btu/ 93.11 cfm of gas
Latent heat of vaporization
86.6 Btu/lb = 583.5 Btu/gal
Total: 39700 Btu/gal
According to...
Guys,
Sorry for not getting back here sooner, just was busy with electrical problems.
Thank you for pointing me to the right direction, Google is really good source of information, but I did not find an answer to my question. I will keep looking.
Hi,
How to calculate how many BTUs it takes to convert one gallon of liquid nitrogen (LN2) into gas?
We use heat exchanger with 280F hot water. Output gas temperature 70F
TIA
davidbeach, you are right. Light photon emitted by the bulb has energy, and this energy transfers to heat, when object absorbs light.
For heat load calculation amount of heat produced by lamp-ballast combination equal to ballast wattage (IMHO).
Gentlemen, thank you for answers
I called tech.support at Universal ballasts (http://www.universalballast.com/productLines/ballast/line_fluor_elec.html) and they told me to calculate loses on the ballast use formula:
Loses = Watts in – Total lamp wattage X Ballast factor
If we will take...
Gentlemen,
Thank you for replies.
Yes, I know about all problems associated with J-box configuration. I will be happy to install S&C Vista line-up, but money is an issue (and physical size of equipment).
Original system (with 3 J-boxes 1in-3out)worked for last 35 years (indoor installation, no...
Sorry, HighPotter... first time poster....:-)
I am looking for metal J-box with copper buss work to distribute 15 kV within the building. J-box will be installed in HV room in the building. 3 phase 600A max. One incoming feed from switchgear will be distributed to 6 substations.