If hot water reset is not available for the boiler, then the idea was to mix the return water with the 180 F entering water. However, if we mix the return water how do we deal with the low pressure of the return water in comparison to the high pressure of the 180 F entering water? Thanks...
The coil has 4 rows, so would it be a good idea to have hot water reset from the 180 F EWT through a mixing valve, (if hot water reset is not available on the boiler)? Thanks for your responses.
For 2-pipe fan-coils, does design CHW gpm have to equal design HW gpm, or can HW gpm be smaller? ie during cooling vfds on pumps would push more water through fully open valve than during heating.
Thanks!