Tek-Tips is the largest IT community on the Internet today!

Members share and learn making Tek-Tips Forums the best source of peer-reviewed technical information on the Internet!

  • Congratulations TugboatEng on being selected by the Eng-Tips community for having the most helpful posts in the forums last week. Way to Go!

Search results for query: *

  1. Ridermike

    PRV hydraulic caculation problem in Autosprink

    I would ignore the PRV on the input and calc as normal, then if your required psi is less than the set point of the PRV your good. If your required psi is greater than the set point, you can look for the psi required at the PRV and make sure that is less than the set point. If not you will have...
  2. Ridermike

    6.4.6.3.2 Pendent Sprinklers.

    NFPA 25 2008 5.5.1.1 Where the original installation standard is different from the cited standard, the use of the appropriate installing standard shall be permitted.
  3. Ridermike

    Underground Fire Service

    Unless the backflow preventor is installed at the entrance, the piping run overhead will have to be approved potable water pipe, unless the water utility allows.
  4. Ridermike

    Unlimited area sprinkler system sizes for Factory Mutual

    Coming in a little late, as far as 10" pipe goes, I have only used it where required for large fire pumps. Split that flow, it will likely be cheaper to run 2 6" mains and the fitters will thank you.

Part and Inventory Search

Back
Top