Eng-Tips is the largest engineering community on the Internet

Intelligent Work Forums for Engineering Professionals

  • Congratulations waross on being selected by the Tek-Tips community for having the most helpful posts in the forums last week. Way to Go!

Search results for query: *

  1. PeterS84

    ROCOF settings

    Thanks for the answer. Why do you think there would be a lot of false trips? If I set the relay to, let's say, 5Hz/s this is some serious ROCOF now and shouldn't happen under healthy conditions. Unless what the relay is measuring and what is actually happening on the system doesn't align...
  2. PeterS84

    ROCOF settings

    I'm thinking about using it as a faster alternative to frequency based load shedding. In case of small inertia of the system load shedding based on frequency may come too late to make any difference (as it takes time for the frequency to fall below setpoint). With ROCOF I was hoping to gain some...
  3. PeterS84

    ROCOF settings

    Hi All, Can somebody give me any guidelines on what settings to use for rate of change of frequency? Would you normally do some simulations before choosing settings or just use a 'generic' recommended one. Also, would you tend to use normal ROCOF or frequency supervised one?
  4. PeterS84

    Capacitances to ground in a substation

    Thanks for the interesting paper! Although the phenomena they're describing there is caused by CT ringdown (energy trapped in the CT after CB has opened) so it's different to the transients caused by charging of the capacitance.
  5. PeterS84

    Capacitances to ground in a substation

    Thanks a lot smallgreek. Since I don't have access to any layout drawings my question was more of an academic nature ;) I was just curious of how much of an impact (if any) it may have on CBFail. A quick calculation for 3m high, 2m to the breaker gives around 0.2nF so not much. For the case of...
  6. PeterS84

    Capacitances to ground in a substation

    Thanks for the information. Sorry if my previous response sounded a bit cheeky - I meant I don't go out to substations so have very little idea about substation design. Perhaps I was looking at a metering CT...
  7. PeterS84

    Capacitances to ground in a substation

    Nope, not that far if CT is on the bushing. However for HV CTs are not always mounted on the bushing (at least that's what I heared). I don't know about the distance - I was hopeing to get some input from people who actually visit a substation every now and then (unlike myself).
  8. PeterS84

    Capacitances to ground in a substation

    Thanks davidbeach. Does this apply to CB fail protection as well? I've done some simulations and it seems that under some conditions the charging current can be in the range of 0.05In and this can last 50-100ms (in those simulations I used capacitance of 5nF per phase which might be a bit...
  9. PeterS84

    Capacitances to ground in a substation

    Dear All, In a substation we have protection CTs in one place and the circuit breakers in another. What I'm interested in is what can be the capacitance of the wire connecting both, or at least the distance between CTs and CB. What I'm trying to understand is how much current (and for how long)...
  10. PeterS84

    Undervoltage blocking of frequency relay

    Not quite sure I understand - with multifunctional IEDs you normally have all three voltages connected and the phase selection algorithm for frequency measurement is internal to the IED, so you never know which phase is the relay actually looking at. Am I missing something?
  11. PeterS84

    Undervoltage blocking of frequency relay

    One more question :) When talking about undervoltage - do you mean undervoltage on any phase or all three phases?
  12. PeterS84

    Undervoltage blocking of frequency relay

    Thanks for all your responses.
  13. PeterS84

    Undervoltage blocking of frequency relay

    Hi All, Any ideas why to use undervoltage blocking for frequency functions (except the obvious one that below approx. 10% of Vnominal the accuracy may not be satisfactory)? I heared some people wanting to set undervoltage blocking to 30% Vnom - are there any reasons to do that? Will these...
  14. PeterS84

    Buchholz / Sudden Pressure Relay

    Does everything said above apply to thermostats (internal to the transformer) as well?
  15. PeterS84

    Buchholz / Sudden Pressure Relay

    OK, thank you all for your replies.
  16. PeterS84

    Buchholz / Sudden Pressure Relay

    Hi All, Can you tell me how do you connect Buchholz/SPR to trip CB - do you connect it directly to the CB or do you connect it via IED's binary inputs (or both - in parallel)? By the way - is there a difference between Buchholz and SPR? Regards, Peter
  17. PeterS84

    CT physical size

    Thanks. [embarrassed]
  18. PeterS84

    CT physical size

    Hi All, Is there any 'magic equation' that allows to estimate the physical size of CT (i.e. length, width, height) based on the turns ratio, VA rating and type of core? How can I actually make sure that the CT will fit where I want to put it (in a cubical for example). I mean protection CTs...
  19. PeterS84

    Applications of distance relays on distribution networks

    By BFP do you mean Breaker Failure protection?
  20. PeterS84

    Applications of distance relays on distribution networks

    Thanks for all your replays. @m3ntosan: Yes, by distribution I mean networks up to 132kV. I'm surprised you mention cables as well - I was under impression that for cables it's mostly current diff.
Back
Top