Thanks for the valuable input.
In conclusion, I don't need a VFD, There is no problem with running a 500HP pump with a 1000HP motor other than some efficiency losses, and a VFD will not help the perceived problem anyway.
Hi,
My client wants to run a 500HP Pump with a 1000HP motor run on a VFD. Is it possible for the VFD to reduce the power output of the motor without reducing the motor speed?
I think if we end up reducing the motor speed, we will compromise pumping capacity as well.
Let me know what your...