Hello everyone
I am designing a protection system for a local grid with one synchronous generator and consumers.
A mechanical fuse (for example, NH 100 A) is installed at every consumer, and one fuse at the generator. A PMG supplies the AVR system, and thus, the generator has short-circuit capabilities by providing a sustained short-circuit in a given period, depending upon the type of short circuit. The Short-Circuit Decremental Curve is to be found at https://www.stamford-avk.com/sites/stamfordavk/files/AGN005_D.pdf in Figure 1 as an example.
The initial maximum short-circuit current is based on the sub-transient reactance Xd'' of the generator . The sub-transient and transient periods decay rapidly due to the interactions between the damper winding and the field winding and the stator winding.
The t'd is 0.03 s, t''d is 0.008 s, and Ta is 0.007 s. I would not expect the fuse to react within t'd + t''d before entering the sustained current state (steady-state). A circuit breaker may react in the instantaneous trip region.
So, I assume that the value of the sub-transient nor the transient currents should not be used to check the breaker time. Instead, I will be using the value of the sustained current. This is a safer approach by guarantee to trip on the sustained current, and hence, covering regardless of the earlier sub-transient spike.
Should I use the value of the sustained current from the Decremental Curve in order to determine the breaker time? I think it would be wrong to use the maximum initial sub-transient current, as this is only a peak value. Also, the generator impedance can be calculated in the sustained period from the decremental curve. I will be using this impedance in order to calculate the short circuit at any buses in the grid. What do you think of this?
The Decremental Curve is only based on a short circuit at the generator terminals.
This approach is inspired by this thread https://www.eng-tips.com/threads/sustained-short-circuit-current-from-synchronous-generator.468321/
I am designing a protection system for a local grid with one synchronous generator and consumers.
A mechanical fuse (for example, NH 100 A) is installed at every consumer, and one fuse at the generator. A PMG supplies the AVR system, and thus, the generator has short-circuit capabilities by providing a sustained short-circuit in a given period, depending upon the type of short circuit. The Short-Circuit Decremental Curve is to be found at https://www.stamford-avk.com/sites/stamfordavk/files/AGN005_D.pdf in Figure 1 as an example.
The initial maximum short-circuit current is based on the sub-transient reactance Xd'' of the generator . The sub-transient and transient periods decay rapidly due to the interactions between the damper winding and the field winding and the stator winding.
The t'd is 0.03 s, t''d is 0.008 s, and Ta is 0.007 s. I would not expect the fuse to react within t'd + t''d before entering the sustained current state (steady-state). A circuit breaker may react in the instantaneous trip region.
So, I assume that the value of the sub-transient nor the transient currents should not be used to check the breaker time. Instead, I will be using the value of the sustained current. This is a safer approach by guarantee to trip on the sustained current, and hence, covering regardless of the earlier sub-transient spike.
Should I use the value of the sustained current from the Decremental Curve in order to determine the breaker time? I think it would be wrong to use the maximum initial sub-transient current, as this is only a peak value. Also, the generator impedance can be calculated in the sustained period from the decremental curve. I will be using this impedance in order to calculate the short circuit at any buses in the grid. What do you think of this?
The Decremental Curve is only based on a short circuit at the generator terminals.
This approach is inspired by this thread https://www.eng-tips.com/threads/sustained-short-circuit-current-from-synchronous-generator.468321/
Last edited: