As I believe you are in NZ, you could use the transmission company's service specification 07.23 (Work site and Mobile Plant temporary earthing and equipotential bonding of transmission lines) as a starting point.
I believe multiple single-point grounding can also be called sectionalised single point bonding, please see Figure 2.4 from CIGRE TB 797 below:
The sheath voltage limiter is essentially 'open', like a surge arrestor, so only one end of the cable is directly grounded. The sheath/shield is not...