    Running TECK Cable In Conduit

    Hi Dan, we asked the same question to one of the Code committee member and his answer was clear: "No you cannot run Teck cable in conduit, you have to stick to the Table 19 as indicated in article 12-100". The reason is that the heat dissipation for a Teck cable in a conduit is «unknown», so...