  1. The Obturator

    Allowable Overpressure for Electric Steam Boilers per ISO-4126

    In a conventional design spring operated Pressure-relief Valve (with closed/pressure tight bonnet and cap), The allowable built-up back pressure is equal to the overpressure. This is a API-520 Pt 1 statement (5.3.3.1.3.). The ARI SAFE valve data sheet advises maximum 10% built up back pressure.
  2. The Obturator

    Allowable Overpressure for Electric Steam Boilers per ISO-4126

    10% maximum built up back pressure for this valve. 'Higher on request' say ARI. Data Sheet https://www.ari-armaturen.com/_appl/files_tb/files/900005-2.pdf
  3. The Obturator

    Allowable Overpressure for Electric Steam Boilers per ISO-4126

    The ARI SAFE is not an ASME I design. Not even ASME VIII, This is a German design based on TUV/AD Merkblatt A2 (aka a 'DIN' valve), but which conforms to the standard ISO 4126 in turn specified and compliant for boilers to EN 12953 FYI: I located a copy of EN 12953 where it refers the boiler...
  4. The Obturator

    Allowable Overpressure for Electric Steam Boilers per ISO-4126

    You should be referring to the latest ASME I (2023), which does not change the subject, however the stated 6% is the maximum MAWP of the boiler (not the overpressure of the safety valve(s)). What was the design code of the boiler installed in Sweden and when was it built? Is it code ('V') stamped?
  5. The Obturator

    Foam Glass Insulation - fire case

    I might be off track here, but you might want to look at Table 5 in API-521 and see how the Environmental Factor 'F' is determined for use in calculation - I must admit your stated insulation is alien to me.
  6. The Obturator

    Allowable Overpressure for Electric Steam Boilers per ISO-4126

    ISO 4126 Limits overpressure to 10% maximum...you can utilise a ASME I design to be fully open at 3% overpressure if you so wish provided the valve design meets PED (if installation is in the EU). (There is an exception in PED to the 10% overpressure limit, but this applies to fire case only -...
  7. The Obturator

    Allowable Overpressure for Electric Steam Boilers per ISO-4126

    @Pavan Kumar You are yet again proliferating queries related to the same boiler subject over several posts and in different forums. This is your 3rd post that I know of the same boiler. Please stop this. You did not even comment on my earlier comments and questions. You also appear not to have...
  8. The Obturator

    Does dry gas PSV always need drainage on discharge pipe ?

    Although you state that this type of vent pipe is a typical design from CGA-G-5.5, it is not of a typical outlet pipe for Pressure-relief Valves meeting API-520,-521,-526, ASME VIII, XIII etc. Note I do not have CGA-G-5.5 to comment more on.
  9. The Obturator

    Does dry gas PSV always need drainage on discharge pipe ?

    We're going to need more info to advise on this. Maybe a sketch/photo? What is the valve type and size (inlet x outlet), set pressure, how is this 'gooseneck' attached and what material is it? (This goose could fly off very easily during valve opening). What API is basically cautioning you on...
  10. The Obturator

    Electric Boiler Question

    @Pavan Kumar - I take it this post relates to your other post in the safety relief valve forum Allowable Back Pressure per ISO-4216 Part9 It would have been better to consolidate this query into one posting so that all contributors to comments can have full visibility (I may have missed the...
  11. The Obturator

    Allowable Back Pressure per ISO-4216 Part9

    Just to be clear, ISO 4126-9 Paragraph 7.1 states "...The allowable back pressure, which is the sum of the built-up back pressure, and the superimposed back pressure, is typically specified by the valve manufacturer or national code or regulation". ie., As I stated earlier, back pressure is...
  12. The Obturator

    Allowable Back Pressure per ISO-4216 Part9

    No different. Back pressure at certain values, reduces the flow. API 520 pt. I explains these scenarios, and what back pressure correction factor is applied to the sizing/flow calculation, based on the type of back pressure and valve type.
  13. The Obturator

    Allowable Back Pressure per ISO-4216 Part9

    There is no back pressure restriction in ISO-4126. Back pressure is limited by the design of the Pressure-relief Valve and is the same as in ASME XIII, API etc. Note that the limits in API-520 stop at 50%. This does not mean that the valve is limited to this percentage. Each manufacture will...
  14. The Obturator

    PSV Serial Number

    Serial Numbers are assigned by the manufacturer (or assembler or repairer - if different) usually against a customer/user specified tag Number. Serial numbers are important when referring any spare parts requirement with the manufacturer, while that tag number maintains visibility of the valve...
  15. The Obturator

    Mininimum Allowable Differential Between Operating Pressure and PSV Set Pressure.

    @_1angelia23 The referenced ASME BPVC 2023 Section XIII 2023 part 9.2.1 (ie., the whole of Part 9 of ASME XIII) is purely a requirement for Pressure-relief Valves undergoing Capacity and Flow Certification. These are the type tests observed and certified by the National Board of Boiler &...
  16. The Obturator

    Mininimum Allowable Differential Between Operating Pressure and PSV Set Pressure.

    For the record. Recommended differentials between operating and set pressure are to be found in current ASME VIII-I (2023) M-10 (c) as copied below (same as earlier edition ASME VIII (2021) M-10 referenced earlier in this post). It does exist. strange that you say you cannot find it. Look it up...
  17. The Obturator

    PSV Blowdown

    @LittleInch 'Blowdown' In Pressure-relief Valve speak, is the term in ASME/API which refers to the reseating pressure of a Pressure-relief Valve. Blowdown is expressed as a percentage against the set pressure. eg. A blowdown of 7% means a valve set at 100 would reseat at 93. I agree though, it...
  18. The Obturator

    PSV Blowdown

    Many factors will ultimately determine how the valve would react in such a situation, such as; design, ratio between calculated orifice area and selected orifice area, ring setting, inlet piping, inlet pressure loss, back pressure etc., etc. Theoretically, a spring operated conventional...