Dear ScottyUK
the following are the details i have in the drawing
Rated output =5MVAR
No.Of Stages =5
Stepsize =1
Rated voltage =11500V
Insulation level =28KVrms
Each capcitor stage contains the following
Air cor damping reactor 250uH,53A
6 no's 201.7KVAR,7303volt...
Hi Guys
Ratings
11KV Busbar Rating=25KA for 3 sec
Operating voltage of the bus bar =11KV
Rated voltage of bus bar=12KV
Rated normal current of bus bar=2500
Power transformer rating =20MVA,33/11KV
In my S/S three transformers ,so in the 11KV incomer-3 & bus section-2 (5 breaker system)...
Hi Guys
I need your attention on the drawing which i sent u in the above attachment
Incomer-1 ,Incomer-2 & Incomer-3 R phase CT they connected to the capacitor bank-1 Auto Power Factor Controller through auxiliary contact multiplication with the condition of Bus section & incomer combination...
Thank you guys for your reply.........here i will attach some of the drawings
Capacitor bank Auto Power Factor Controller CT input selection
1) Capacitor bank-1
a) If I/C-1 CB closed R-phase of the CT will come to summation CT of APFC
b) If I/C-1,B/S-1 & I/C-2 closed R-phase of I/C-1 &...
Hi Guys ,
3*20MVA S/S
Transformer 1&2 have the same percentage impedance
Transformer 3 have the different percentage impedance
My question can we make parallel opearation of transformer 2&3?
Thansk & Regards
Raja.P
Hi everyone,
I am Raja, i have some technical doubts ,i am working in 33/11 KV substation with 3 20 MVA(33/11.5KV) transformer
1) 11KV SWG SEC-A,SEC-B & SEC-C (three incomer & 2 Bus section scheme)
2) 5 MVAR capacitor bank for each 11KV SWG( SEC-A,SEC-B & SEC-C)
My doubt when incomer-1 in...