STOOKEYFPE, THANK YOU FOR YOUR RESPONSE, I WILL HAVE THE ELECTRICAL CONTRACTOR INSTALL HEAT TRACE. I WILL CONTACT TYCO AGAIN AN GO OVER THE INSTALLATION, CONTROLLERS, MAINTENANCE SCHEDULE REQUIRED.
I called tyco and explained to them as how I plan on using this heat tape. they assured me that for my application it would be allowed.
I am going to submit copy to our local fire prevention bureau for review. to make sure they will allow this product to be used.
working on project existing heat treat facility, existing oil quenching protected by co2 system. the remainder of plant has 9 furnaces.
my question is my design of .30.3250 with 500 outside hose. entire facility will be dry systems. there may be some areas that could be reduced such as...
I AM CURRENTLY IN THE BID/DESIGN STAGE OF A MJ FACILITY, CEILING HEIGHT IS ONLY 14FT, THEY STATED THAT THERE PRODUCT WOULD BE 3FT BELOW CEILING HEIGHT. I BASING MY QUOTE ON OH2 THROUGH OUT THE ENTIRE PROJECT. THERE WILL BE NO "EXTRACTION" AT THIS LOCATION.
BASED ON YOUR STORAGE HEIGHT I WOULD...
THANK YOU FOR YOUR RESPONSE, HERE IS WHAT I CAME UP WITH, CLASS IV, BLD HEIGHT MAX 20FT, IF THE BLD HAD BEEN LESS THAN 16 I COULD HAVE GONE WITH OH2, BUT BEING MAX 20 I WENT WITH EH2, PALLETIZED STORAGE HEIGHT 5 TO MAX OF 10FT.
READING NFPA495 IT SEEMS THERE MORE CONCERENED WITH THE PLACSTIC...
i have a project that owner will be storing ammunition on pallets on the floor there looking to store 60,000 to 80,000 pounds of ammo. I have read thru nfpa 495 but do not see any mention of density
would oh group 2 be statisfactory?