@jghirst,
Correct. When I do calculation its 2400 Amps. So considering balanced 3 phase, it is 800 Amps per phase.
So it means 4 runs of 120 mm2 should be good enough per phase (344 amps per run). Total 12 runs of 1 core 120 mm2 cables.
Hi,
Jghrist - You are correct, my bad.
I intended to say is 8 runs of 3 core 240mm2 cables as per calculation for 2400Amps, 3 phase current.
But when I select 1 core 120mm2 cable, then I see that 4 runs 1 core 120 per phase should be sufficient. So it makes 12 runs of 1 core 120mm2 cables...
Hello,
I have 690V network, 3 phase system, no neutral, with 2400Amps load current.
I end up with 8 runs of 3 core 240mm2 cable size.
When I select 1 core cable, I can manage with 12 runs. It means only 4 runs per phase.
3 core cable in general has low current capacity than single core.