I m not an expert in the field of executing and designing road
but I m working on an electrical substation project
Where I should submit the design of the access road
And I have this small issue
The area next to the site is super flat so i need to backfill couple of layer of subgrade and...
Hello
I m building a road in a flat area so I need to rise the road one meter above natural ground level
Any idea what should be the slope of my fill for one meter height ?
If you can send me a reference it would be perfect
I totally agree
But the consultant required 28 days
This will delay my progress on site for 2 weeks
And with no article ,code or reference I wont be able to convince him
Hello
I am driving piles for a building
And I want to start casting pile caps but the consultant didn't allow to cast any concrete structure while driving
Do you have any reference concerning this issue ?
THANK YOU FOR YOUR REPLY AND SORRY FOR THE DELAY
THAT'S A SKETCH OF THE STRUCTURE (ATTACHMENT)
ITS A BUILDING RETAINING WALL
SO I DON'T THINK I HAVE AN OVERTURNING PROBLEM
EXISTING WALL THICKNESS 30 CM THE NEW ONE I SHOULD ADD 30 CM SO 60 CM
WHAT I ' M ASKING IS THE CONNECTION BETWEEN THE...
I need to increase the height of an existing retaining wall from 5 to 9 m .
The overall stability of the structure is checked.
BUT i need to increase its thickness .
Should i use bars anchored bars with epoxy to make sure that the two structures are working as one
In intermediate moment frames should i use for bars development the eqt of 21.7.5 or the eqt of 12.2.3
What i m sure of is that 21.7.5 eqt is used for special moment frame but should we use it for intermediate too ?
Thank you for you reply
but in my case
1)i cant use smaller bars
2)As provided = As required
3)for headed bars ldt is greater than my column width .
Here i have a question:
The 90 degree hook length should be min 12db.
Do you know if i can extend this bar ?if yes can you send me the reference...
THE CONNECTION BETWEEN COLUMN AND BEAM, IF THE WIDTH OF THE COLUMN PARALLEL TO THE BEAM IS LESS THAN (Ldh) OF THE BEAM what can i do ? Column width could not be change
I have a second question developement length is for no.10 to no.36 what if i have no.40 what Ld be ?