  1. SilFox

    Distribution of the programs

    Distribution of the programs Where brains? Please clear the following situation. We have the freely programmed controller (s),and we have the computer with the scada-program, which exchanges the data with the controller. In the controller is placed the executed program,but in the computer...
  2. SilFox

    Improper air flow, I think.

    Hi elfman! Though you don't specify an exact arrangement of air supply grilles, it is supposed that some of them are located below. I think it is useful to check up the air stream from them simple by a hand. Be sure that is not present any obstacles for it passing.Many of grilles have...
  3. SilFox

    Lab exhaust fan control

    Dear SAC9! That I've caught. In connection with a condition that you want to ensure constant flow of exhaust air by means of baypass you will take a part of air passing HERA filters. In such case it will result in incorrect work of these filters. Concerning control of the damper I can offer...
  4. SilFox

    new home ,air changes per hr?

    In first I want to thank dear KenRo for his attentive amendment.Sorry, Now all is correct. Further, concerning a discussed theme, I shall state some more small remarks. It is doubtless, that the value, laying in limits from 0,35 ANI to 0,6 ANI is closest for home application,however it is...
  5. SilFox

    new home ,air changes per hr?

    Here complete version www.rebuild.org./attachments/guidebooks/ventilation.pdf Regards
  6. SilFox

    new home ,air changes per hr?

    Hi sam42! Some more information... From the building code perspective, adequate ventilation refers to that level of ventilation that protects the health and safety of its occupants. Most regions of the U.S. have building codes that specify ventilation levels for new buildings. Some regions...
  7. SilFox

    Buffer Tank

    Hi! The technological process works with sharp rises of temperatures.(10F/20s) It's necessary to mix water so that: 1. Occurred initial heating of water practically immediately - for activation of chiller's loading system 2. The change from a minimum to a maximum must occured extended in...
  8. SilFox

    Buffer Tank

    Hi all! CHWS for process aplication What best way of an arrangement pipes of input and output in buffer tank for obtain of gradual change temperature, at heat impact from loadings (at one level, one is higher than another, to arrange above, below, in middle)? How to calculate its(tank)...
  9. SilFox

    Dust collection & static dissipation

    Hi Markac! The difficult enough problem to me, m.b. to try any antistatic elements - metal filters, metal inserts in the duct,with grounding?
  10. SilFox

    chiller's shoot-off valves

    This question is connected to a method of regulation the necessary difference pressure on evaporator in case of small heat loading, but plenty of the consumers . The variant is considered for VarPrOnlySys. Unique, that anxieties me, it's passage of the cooled water through evaporator. I...
  11. SilFox

    simple air flow problem

    I think it's might be so: Required flow can be calculated according to Q = H/c*p*(Ti - To) assume that H = 205kWt or 11658 Btu/min, c = 0.24, p = 0.075, Ti = 30C or 86F, To = 40C or 104F, and Q = only 35981 CFM.
  12. SilFox

    BMS reading for chiller

    Hi bundy! 1. The real chiller's capacity can vary depending on loading. 2. Try to use the following formula: TR = Flow(l/s) x Evap.Range(deg C) x 4.187 x 0.2844
  13. SilFox

    chiller's shoot-off valves

    Hi all! As is known, obligatory attributes, necessary at installation chiller, are so-called shoot-off valves. I am not quite sure, but I assume,that it's made for when chiller does not work, the pump consumed smaller power (1), and that the cooled water did not proceed through...