I'm looking at a vessel vent line, which will be used to manually depressure a vessel containing light natural gas at 100 barg to an atmospheric vent header. The line is equipped with a restriction orifice and downstream of the RO passes via several collection headers, all of increasing size...
OK, thanks Latexman for getting the ball rolling.
Yes, the separator is typically 30%-60% liquid filled (oil + produced water). So my understanding is that the total relief load for fire case is vapour generation from heat input to wetted area (Eq.(3/4) in API521) + expansion of gas in the...
Colleagues,
When performing a fire case relief calculation, API521 equation for heat load against wetted area (Q=21000A^0.82, etc.) will give a relieving load due to vaporization. Do I also need to include an additional load due to gas expansion in the vapour space (Equation 8 in API521, W =...
Montemayor
I will forgive the abrupt opening to your response on account of your long history of politeness and patience. I was merely asking for an order-of-magnitude feel, not a transcript of the calculation, hence the lack of data supplied. Two of your final three sentences were sufficient...
Does anyone have a feel for (or ideally some reference to) how far UPSTREAM cooling will take place in the pipe wall at a valve in gas service with a high dP.
In other words, a hydrocarbon gas at ~140 bar is depressured to flare (atmospheric + nominal back-pressure) via a globe valve. Valve and...
The Cp/Cv value in Hysys is the 'actual' value, based on the equations of state in thermodynamic package you are using.
You can calculate the 'ideal' value by the following formula:
Cp/Cv (ideal) = Cp / (Cp - R)
where Cp = molar heat capacity of gas stream (kJ/kmolK)
R = universal gas...