Eng-Tips is the largest engineering community on the Internet

Intelligent Work Forums for Engineering Professionals

  • Congratulations waross on being selected by the Tek-Tips community for having the most helpful posts in the forums last week. Way to Go!

Search results for query: *

  • Users: coingy
  • Order by date
  1. coingy

    Friends, Our client has 6.6kV sy

    Faulty, There should be no need to change any surge arresters if you change the NER. I assume the request to increase the value of the NER is to limit the fault current to the value of tyhe full rating of the largest Generator of Transformer. They are slighly inductive and this can be a...
  2. coingy

    Electric System Fault Calculations - MVA Method

    Hi BigJake, Further to my previous answer perhaps this may be of more use. It is nescessary to convert all reactances to a common kVA or MVA which ever is your preference. The value of this base is quite unimportant and may be, 1. That of the largest plant 2. That of the total plant capacity...
  3. coingy

    Power generation, circulating current problem

    Skeandhu, In order to share correctly you should have the controls set for droop (as Bigamp states) and the AVR's and Governors set regardless of rating of the sets to the same settings, typically 4%. Having one set in Isoch will cause problems as its flat response will fight for the load or...
  4. coingy

    Running at FLA

    dougjl, Before the days of the "bean counters" an old engineering rule of thumb was to size motors so they ran at 80% of the duty thus giving the spare capacity required. I still apply this rule but just don't advertise it too much. Cheers, Coingy
  5. coingy

    start capacitor sizing

    Acmebunny, It could have a capacitor of size up to 800 mfd. Cheers Coingy
  6. coingy

    start capacitor sizing

    Acmebunny, For the custom fit method using busbars physical size method. First make available the capacitor leads and both sides of the start winding. Apply power to both the start and run windings with the rotor locked. The voltage across the capacitor and the start winding should be recorded...
  7. coingy

    Acceptable Test Values for new 2KV cable.

    EP, Our company standards would be a 1kV megger test with a minimum IR of 100 Mohms. It is not a normal test for a PI on a cable and I am not sure why this has been specified. A PI minimum of 2 is for equipment. Cheers, Coingy
  8. coingy

    circuit overload protection vs overcurrent

    Isaacs, Overload and Overcurrent should not be confused as the protection relays perform completely different functions. An overload relay operates in the hundreds to thousands of seconds range whereas an overcurrent relay operates in the one to ten second range. Cheers, Coingy
  9. coingy

    Electric System Fault Calculations - MVA Method

    Hi jake, Years ago a Dutch colleague of mine when I was working in Holland gave a pamphlet for short circuit calculations which I refer to on and off as required. The address on the pamphlet where you may be able to obatin a copy is:- Point-To-Point Method For Short Circuit Calculations...
  10. coingy

    Transformer Inrush Current

    The rule of thumb I've always used is 6 x for large transformers, say, 2MVA and above. The smaller transformeres due to the larger inductances can be 14 x.
Back
Top