  1. BrandtK

    ANSI C119.6-2018 bus bar 950A current cycling testing - how to reduce resistance swing?

    Thanks - do you have a grease you would recommend for this purpose? The set screws in use would be tightened very occasionally.
  2. BrandtK

    ANSI C119.6-2018 bus bar 950A current cycling testing - how to reduce resistance swing?

    hi, The subject resistance is the system of an aluminum conductor supplied by the test lab, plus the bus bar assembly (bar plus the wire mounting hardware which are a sliding receiver and a big set screw). We have no control over the preparation of the aluminum conductor; all we can control is...
  3. BrandtK

    ANSI C119.6-2018 bus bar 950A current cycling testing - how to reduce resistance swing?

    We are developing a bus bar for a utility customer that wants a C119.6 certification. The test spec they require involves 500 four-hour current cycles at 950 amps, 2 hours on followed by 2 hours off. Resistance is measured in micro Ohms and once a baseline resistance for the bar assembly (bar...