to viperone:
There is one case where the part winding start leads are larger. For 9-lead, delta connected, dual voltage, suitable for PWS on the low voltage, the 1-2-3 leads are normally larger than the remaining 6 leads. However this is for cost reasons rather than current sizing
Also some...