  1. Maak

    Arc Flash

    Instantaneous trip without jeopardizing coordination is possible by dedicated arc-flash protection, based on simultaneous sensing of arc-flash light and overcurrent. Very common in some countries, both in utility as well as industrial installations (MV and LV).
  2. Maak

    Arc Flash Hazard Analysis

    I agree with "jghrist" and "davidbeach". Some people seem to have serious attitude problems related to light & overcurrent based systems which provide the fastest protection and lowest incident energy. Because several major manufacturers are turning to this well-known technology, there is a...
  3. Maak

    1/2 Cycle fuses and Arc Flash Energy Levels

    IEC 62271-200: "Application of suitable current-limiting fuses in combination with switching devices can limit the short-circuit current and minimize the fault duration. It is well documented that the arc energy transferred during such tests is not predictable by I2t. In the case of...
  4. Maak

    NFPA 70E archflash

    "Arc flash is only relevant when someone is working on the energized gear." I strongly disagree. Don't you think about a) damage to the equipment and b) costs due to interrupted processes? Safety first, but it is definitely not the only issue. There are better solutions than maintenance switch.
  5. Maak

    Mitigation of Arc Flash Hazard on 3000kVA txfmr feeding 480V swgr

    Current limiting fuse is a good option only if you can guarantee that the current will be high. In low voltage systems the arcing current is often less than 50% of the bolted fault current. "In the case of current-limiting fuses, the maximum arc energy may occur at current levels below the...
  6. Maak

    Incident Energy with CL Fuse Equations

    Arc eliminators can detect (optical detection and very fast overcurrent detection) AND eliminate the arc within a few milliseconds. Manufacturers say that arc burning times of 2ms (LV) and 5ms (MV) can be reached. Thus a combination of a crowbar and a CL fuse would provide 1) very short arc...
  7. Maak

    Incident Energy with CL Fuse Equations

    At low voltage the arcing current is often less than 50% of the bolted fault current (can be less than 30%). No wonder an IEC standard puts it this way: "In the case of current-limiting fuses, the maximum arc energy may occur at current levels below the maximum interrupting rating." (IEC...
  8. Maak

    Arc Guard Equipment or Transformer Differential Protection

    dpc wrote: "The optical systems promise faster response, but there are possible issues with retrofit of optical sensors on existing equipment." I would like to hear what kind of issues there are. As far as I know, retrofit of optical sensors is rather easy. Optical systems (often combined with...
  9. Maak

    O/C Relay Settings For Arc Flash

    Use either dedicated arc-flash protection relay or a numerical relay with arc-flash option. With trip initiation time of only a few milliseconds you increase safety and significantly mitigate damage to equipment and thus limit costs due to process interruption. Choose fast circuit-breakers...
  10. Maak

    Distributed Generation!

    I believe E.J. Coster has examined these issues.
  11. Maak

    Arc Flash Mitigation

    Time to find out how optical sensor based arc-flash protection could help? It is de facto standard in some countries. If only a very short arcing time is allowed, the answer is arc eliminator. Manufacturers with a lot of experience: ABB and Vamp.
  12. Maak

    Shorting a fused switch for Arc Flash

    Current-limiting fuse is very fast IF the current is high, but if the current is lower than bolted-fault current, as it is often in arcing faults occurring in LV systems, ... You could consider dedicated arc-flash protection products to guarantee high speed protection --> low incident energy.
  13. Maak

    Arc Flash protection

    I believe VAMP has been on the arc-flash protection market more than 10 years, the first years with a different name. For special purposes both VAMP and ABB sell arc eliminators that can extinguish the arc within 2-5ms. With conventional optical sensing based protection the arcing time is the...
  14. Maak

    Arc Flash Virgin

    See IEC 62271-200. There you can find some information. In some European countries de facto standard in arc-flash protection is light and current based protection (optical sensors). This method is recognized by the IEC standard.
  15. Maak

    Ripple Control Signal

    Has anybody studied how Ripple Control Signal behaves during power system disturbances, e.g. voltage dips? Does the signal totally disappear or attenuate very much? For my purposes, a continuous signal is needed.