@LCREP
The auditor has visited the site before CoVid (2019) and n much of discussion has taken place afterwards. Site owner now wants a proposal on how to meet the demand, which is to be discussed and agreed with insurance team, and then introduce corrective measures. That's the whole plan...
@LCREP - We were only provided with what they (Insurance)need to be achieved. No any advice given.
But I guess I found a way to manage it -In-rack protection independent of ceiling - 25.8.1.8 and 25.8.1.10
@CDAFD - Image link is not working - "Page not found"
Many thanks for both of you!
Dr...
Hi UFT12!
This is not in USA, In Sri Lanka. There's no any qualified people around to get them to visit and see.
I'm trying with Chapter 25 now to try and combine In-rack with it.
Individual flow, when tested after opening 8 sprinklers at the same time, the lowest was delivering 138 l.p.m. and...
Hi!
Thanks for the reply.
Yes, I have seen 21.1.4 and trying to solve the issue by sticking to 21.1.3(Use K80) as the site has much more sprinklers than 10.2.4.2.1(d)specified minimum(Over designed)to provide a coverage of of 8.8 m² per sprinkler.
Appreciate your comment.
Thanks!
Dr. Rohitha...
Good day Elites!
I'm having a challenge in updating the sprinkler fire protection system of a 50 year old cigarettes manufacturing and storage facility and have faced some challenges.
Dimensions of each storage - 20 x 22 meters, Roof height 7.5 meters and sprinklers mounted here.
Storage rack...