Hi,
May I seek some advice regarding BS 7430 requirement on resistance to earth.
I see in Annex A regarding legislation (the Electricity Supply Regulations), it states resistance to earth has to < 1 ohm. I think it's referring to TN-S system.
But how about TT system?
And how about the HV (or...
@catserveng,
Thanks a lot for the information provided, much appreciated your help. Just also wondering if there is a separate section called "Piping system basic information" available, as it is being referred in the "Diesel fuel and Diesel fuel systems" section.
Many thanks
P
Thanks TugboatEng. I understand the general principle to size any pipes or ducts for fluid or air. But I'm wondering if there is any chart or table that is available for diesel fuel and generator exhaust hot gas so that I can use to check the fuel pipe size and the chimney size, same as that we...
Hi,
Could anyone please advise me any formula or chart / table for sizing of fuel pipe and the exhaust chimney of a diesel generator?
The chimney needs to run vertically to tens of meters above the generator location within a building.
Thanks
PMCH
HI,
May I know if there is any rule of thumb to reserve the breaker provision for future capacitor bank and active harmonic filter in an electrical system - i.e. sizing the breaker for the future cap bank and AHF. The reason is that at the moment of design, we don't have any information about...
@nuuvox000
the humidity range I described must be maintained. I'm just wondering if the chilled water coil can already do the job without a dehumidifier. Though the load is basically near to 100% of sensible load, we may still have a bit of latent load due to infiltration, or if there are...
@nuuvox000
Basically I'd like to understand how to determine the pressure drop of the air path if a flooding system is used, e.g. a pressurized raised floor system with the AHU just immediately connected to it with air outlets at various locations. I see such kind of raised floor design...
Hi,
May I have some advices on air flooding system. Assume I have to design an air flooding system, e.g. a pressurized raised floor, how to estimate the air pressure drop of this flooding system in order to size the external static pressure of the AHU ?
Thanks.
Hi,
I've a case where it requires an indoor air conditioned environment be maintained at 16 to 25 degC and 20% to 50% RH, for tape storage equipment. Assume the load basically is sensible load (tape storage equipment only). If just using a normal chilled water system, e.g. 7 degC supply and 12...
The two sources ultimately coming from the same utility feeder, so suppose won't have major difference between their phase angles if they are in the same phase, e.g. L1, right?
However, if the inputs are from L1 and L2, then the difference might not be expected to be minor right? Given we don't...
Hi,
Would like to seek some advices on STS. The design consultant designs with the source 1 and source 2 input to a single phase STS in different phases (e.g. S1 on L1 and S2 on L2, S1 and S2 originate from different power transformer). Assume this is incorrect / bad practice as normally S1 and...
@ thermionic1
We have 2 cases: 1. single genset not connecting to grid any time. 2. multiple parallel gensets, also not connecting to grid any time.
Thanks