Thank you for response
@Che12345 Refer to my below message and your response , Please advise the number of ground rod and size , thank you
1. Neutral of Genset will be grounded . 20mm copper 3 mtrs rod is enough for Grounding ? Conductor size between neutral of Genset and Grounding rod ...
Dear Che12345 & xnuke
Thank you for your response .
From your relies followings are clarified :
1. Step up transformer .4/11kv yNd11 that LV side is Delta and MV side is star and solidly grounded
2.Gensets neutral will be soldily grounded
3.There is no requirement of Neutral bus bar in...
We have 1250kva two generators of CAT which is giving output of 400voltage . These genset will be connected to synchronizing panel. After Sync Panel we will connect it with 2500KVA step up transformer .4/11kv .
This transformer will convert voltage into 11kv . vector group of this transformer...
thank you for ur support ,
We will ground the neutral of generators , 2 x earth pits with 20mm x 3mtrs copper rod with grounding enhancement furse - cement for each generator Neutral . Generator body will be seperately grounded through seperate earth pit .will it ne enough . please guide ...
We have 1250kva two generators of CAT which is giving output of 400voltage . These genset will be connected to synchronizing panel. After Sync Panel we will connect it with 2500KVA step up transformer .4/11kv .
This transformer will convert voltage into 11kv . vector group of this transformer...