Speaking for transmission level IEDs at least, as lower end IEDs mean reduced price levels, meaning reduced capability and more basic technology:
To a certain extent it can. Binary input and output modules do have self supervision or watchdog supervision and detecting if a particular module...
Depends where you ask ^_^
Nah, development has been shared between Baden and Västerås for a while now, only the actual product sales are centralized in Västerås. System sales is mostly from Baden, especially big projects.
I think the single PCM600 with the separate connectivity packages is the best you're going to get. Since although the Sweden / Switzerland split in transmission level protection products is gone, there is still the division between transmission and distribution (Finland) protection products. And...
You can find the software here:
https://dl.dropboxusercontent.com/u/72812009/ABB_RE_16_Jun%2007_Light.msi
And actually it is called CAP316 in some places (CAP2_316), noticed it when running the installer. Didn't even realize that before.
The 316 series is not in PCM600 (since RE*316 is not Relion, too old essentially and in a legacy phase).
CAP316 doesn't exist, but CAP540/505 was/is used for the Swedish / Finish relays (500 series), while the RE*316 came from Switzerland.
I can check tomorrow if I have the RE*316 software...
True from a thermal point of view, it's about thermal mass, environmental conditions, the pre fault / overload temperature and duration of the overload. Even so, treating the transformer as an uniform object that heats and cools down as a block is at best incorrect (and incidentally a reason I2t...
In the end they all do the same though, measure if the I0 is above the set threshold value. The IED doesn't really care if it's a core balance CT, neutral point CT or internal / external 3I0 summation.
Actually it doesn't show 50N in that table. Maybe 67 was intended as non time delayed and non...
64 is measured with a single phase CT on a earthing point, 51N is through 3I0, 51G I've only seen in ANSI (ok, it IS ANSI, but I haven't sene it used in IEC), but I've been told it refers to a neutral point CT again. So to me 64 = 51G. But 51N is different, measurements wise anyway. Completely...
The Reyrolle one is now Siemens I believe.
Still looking for the BBC manual, but I found the ASEA one.
One downside / no English. French, Italian or German, take your pick. Reason being the relay was mostly sold in those markets.
https://www.dropbox.com/sh/0udvkkcc6ujhtis/LmBvFOrF8q
There's...
Sure, no problem. Generally speaking we have all old manuals still available, but many of them haven't been scanned. Just let me know if you need any other BBC / ASEA manuals.
Here's the datasheet and the manual:
https://dl.dropboxusercontent.com/u/72812009/CH-ES%2062-91%20E_LI6-LIZ6.pdf
https://dl.dropboxusercontent.com/u/72812009/CH-ES%2082-91%20E_LI6-LIZ6.pdf
Old stuff though. Definitely time to replace it.
Yes, there are many different firmware versions for both types of HMI. And like Dimitiko wrote, it is generally best / recommended to use the configuration software for that specific release.
It's been years since I've used one, but I expect the firmware revision to be printed on the label on...
The REF542+ can't be configured with PCM600. PCM600 is only for the 615, 630, 650 and 6570 series of IEDs.
There is a connectivity package for the REF542+, that's the one you installed. But it's only useful for IEC61850 systems. It serves only the communication board in the REF.
So in order to...
Hi submonkey,
That's quite ok, CAP505 did make the MicroSCADA account after all, that's true.
PCM600 installs MS SQL server 2008, which runs its own services and in addition a SQL Server (PCMSERVER) and server agent.
In the same line, IET600 (61850 tool) install its own SQL server (IETSERVER)...