Morning All,
Just would like to thank all for the help in the past.
This maybe a silly question,
I have mag.curve results for a multiple ratio CT (200/400/600/5)5P20 10VA.
The Mag. curve was done on the 600/5 ratio - full tap, knee point voltage =98V
On the same class (5P20 10VA), but a...
Good day Gents,
Durring the pre-commissioning testing of a 11KV mobile modular (11KV switcgear & associated equipment).
Found the Voltage Transformer connected to the 11KV Trf. Circuit Breaker has the middle phase(White phase) earthed reference and the primary side star point floating (no...
I work for a utility group and had contractors perform Mag. curves on our 110KV post CT's with the following results:
CT ratio & Class - 1600/1200/1000/400/1A 1.0M - 10VA
''A''Phase Tap (8.23Ω) ''B'' Phase Tap (8.25Ω) ''C''Phase Tap 3.45Ω
X1-X2=240.37V X1-X2=239.57V...
Hi hope you can help.
I can not find in the AS/NZS 3000 wiring rules, if Two-core and earth flat cable is required to be mechanically protected.
The contractors have used this cable between the 415V AC board and 240VAC socket outlets & Sump.
I would of thought that this cable would require...