Continue to Site

Eng-Tips is the largest engineering community on the Internet

Intelligent Work Forums for Engineering Professionals

  • Congratulations MintJulep on being selected by the Eng-Tips community for having the most helpful posts in the forums last week. Way to Go!

Search results for query: *

  • Users: bdfig
  • Order by date
  1. bdfig

    Bus 1sec fault rating vs IEC 60909-0

    Hi Kiribanda, Is there a standard (preferably IEC or AS) which specifies this? I certainly support this approach(especially since the switchboard does not have a shorter time rating). However I have been getting some pushback saying this is overly conservative, and would like something concrete...
  2. bdfig

    Bus 1sec fault rating vs IEC 60909-0

    My question is for the generators in my network, which impedance (sub-transient, transient or synchronous) is used when trying to establish if the 25kA/1sec fault rated bus is adequately rated.
  3. bdfig

    Bus 1sec fault rating vs IEC 60909-0

    Hi, I have a bus which has a 25kA/1sec fault rating. Is this normally compared to IEC 60909-0 sub-transient, transient or steady state fault level? Any help is appreciated.
  4. bdfig

    IEEE 1584 Equation 4 Units

    Jghrist, ignoring appendix E and only looking at Section 5.3: En is in J/cm^2 and E is in J/cm^2
  5. bdfig

    IEEE 1584 Equation 4 Units

    What I am saying is that IEEE 1584 provides the following formula to convert from normalized incident energy to the actual incident energy: E = 4.184*Cf*En(t/0.2)(610^x/D^x) And E and En are both in J/cm^2. Therefore why do we have a 4.184 factor?
  6. bdfig

    IEEE 1584 Equation 4 Units

    If En is in J/cm^2 and E is in J/cm^2 then why are we introducing the 4.184 cal->J conversion factor.
  7. bdfig

    IEEE 1584 Equation 4 Units

    Hi, in IEEE 1584 equation (4) (page 11) it states "En is the incident energy (J/cm^2) normalised..." Then in equation (6) E = 4.184*Cf*En(t/0.2)(610^x/D^x) E is the incident energy (J/cm^2) and in section E.3.1 Equation (E.1) E= Cf*En*(t/0.2)(610^x/D^x) in cal/cm^2 Is En from equation (4) in...
  8. bdfig

    Instantaneous Override Current (ABB Tmax)

    ABB SACE Protection and Control Devices appears to show that the instantaneous setting can be turned off (I have attached the relevant page). Also Icu and Ics are much higher than the instantaneous override maximum...
  9. bdfig

    IEC 60909 Transformer Impedance Correction Factor

    Should the impedance correction factor be applied to the minimum fault calculations aswell or only the maximum fault calculations? I have seen a similar question to this where there was debate since the formula only mentions cmax, but not cmin.
  10. bdfig

    IEC 60909 Transformer Impedance Correction Factor

    Hi, I was wondering what reason is behind IEC 60909's transformer impedance correction factor. Is this replace transformer impedance tolerance, or should they both be applied?
  11. bdfig

    Instantaneous Override Current (ABB Tmax)

    The reason I though it might have one is that in the ABB white paper "Working with the Trip Characteristic Curves of ABB SACE Low Voltage Circuit-Breakers" Figure 13 shows a TCC of the PR222DS/P-LSIG (with Tmax T4H250 CB) with I protection not activated. In the figure, the Instantaneous Override...
  12. bdfig

    Instantaneous Override Current (ABB Tmax)

    Hi, does anyone know what the instantaneous override current of an ABB Tmax T4S circuit breaker with PR222 trip unit is? I cannot seem to find an ABB document which has this.
  13. bdfig

    ETAP LV Circuit Breaker Opening Times

    Hi dpc, is this also the case for electronic trip units? Specifically I am looking at curves from PR222DS/P trip units for ABB T4S and T5S circuit breakers, and PR331/P trip units for ABB T7H circuit breakers.
  14. bdfig

    Circuit Breaker Uninterrupted Setting

    Hi all, I am currently using ABB circuit breakers, which has an uninterruptible current rating equal to their frame size. However the long time pickup of their associated trip devices has a tolerance of 1.05 to 1.20. Does the continuous current rating of the CB preclude me from using the...
  15. bdfig

    ETAP LV Circuit Breaker Opening Times

    Hi all, In ETAP I have added LV circuit breaker opening times in the "Min. Delay" field under the Ratings Tab. However the opening times do not appear in the sequence of events or arc flash study results, and the arc flash fault clearing times appear to just use the trip device TCC time at the...
  16. bdfig

    ETAP Cable Zero Sequence Impedance for L-G faults

    However, doesn't the 3*Zn come about, because the zero sequence currents are in phase, and all travelling on the return path (so the algebraic trick is to change 3*In*Zn to In*(3*Zn))?
  17. bdfig

    ETAP Cable Zero Sequence Impedance for L-G faults

    dpc, when you say ETAP should be able to explain their methodology and what their Z0 represents where do you think I can get this information? I sent an email to ETAP's help desk, but they have not responded. Also redfurry, I believe Zn includes the zero sequence impedance of the return path...
  18. bdfig

    ETAP Cable Zero Sequence Impedance for L-G faults

    My understanding was that for a single line to ground fault If = 3*V / (Z1 + Z2 + Z0 + 3*Zn) With V the phase line to neutral voltage, Z1, Z2, Z0 the sequence impedances of a phase line, and Zn the zero sequence impedance of the neutral conductor. I guess what I am after is how does the zero...
  19. bdfig

    ETAP Cable Zero Sequence Impedance for L-G faults

    When attempting to validate IEC 60909 L-G fault calculations from ETAP, I find that the fault levels are higher than I calculated. It appears that ETAP is doing Sqrt(3) c U / |2*Z1 + Z0|, with Z0 taken directly from the R0 and X0 in the cable library entry, rather than using Z0 = Z0 phase...

Part and Inventory Search