Thanks, it sounds like its not a good idea to go any higher. The gen set is actually a 1.2mw instead of a 2mw. It's an old Brown Bavari 1200rpm. I left out some information in that there is a step up transformer Wye-wye between the gen set and the capacitor bank. The capacitor bank is at...
The factory default on an Easygen 3000 for generator load unbalance is 15%. Our generator is set up to load share with the utility. We have a fused capacitor bank on the load side of the utility recloser. Gen set is 2mw and the load runs below 700kw. Cap bank has(3)200kvar units, one per phase...