For your external static pressure loss use the furthest and most restrictive run of duct from the fan inlet to the last air device. Just to make sure, you do not add all of the fitting losses from every branch, add the external static for the furthest or most restrictive run of duct. Take into...
Sounds good thank you. The landlord has a Structural Engineer so I will have to cover the exact placement with notes and have the Structural Engineer review before any penetrations are cut on the roof. Thank you so much for your advice.
Thank you Ron. Now if the HVAC unit curb is not large enough to span the distance between joists (5 foot) I wonder if the equipment curb can just be placed on the metal deck. It states that the girder panel point load includes 1,500 roof top unit load...
I am unclear on a note on structural drawings. I have to place two HVAC units on the roof and the drawings state the following- The roof framing design includes one or sum of roof supported mechanical unit(s) weighing no more than 1,500 lbs. supported by at least two joists per bay. (adjacent...