This was confirmed using a new capacitor same nameplate and a removable resistor. Rated at 72-86µF with no resistor read 78µF, with resistor read 135µF.
So I am guessing the multi-meter takes its reading based on the RC time constant, so by adding impedance it changes the "capacitance"...
I have two centrifugal 3HP single phase submersible sewage pumps, which use 2 start caps (rated 72-86µF) wired in parallel and 2 run caps (55µF) wired in series to operate. These pumps have been failing out due to overtemp during high flow conditions, so "continuous" running. I believe I need...