Thanks Stookeyfpe,
The State adopts NFPA 1 and NFPA 101, as well as portions of the IBC, etc. (ICC = International Code Council i.e. publishers of the IBC, etc.)
Compliance with NFPA 110... So 2 hour enclosure it is.
Thanks!
Hi All,
What if any is the Fire Resistance Rating for a room enclosing an Emergency Power Supply (Generator Room) in a parking Garage (including Code references Please).
I am currently look at:
NFPA 110 Chapter 7, 7.2.1.1 requires the Emergency Generator room to be in a 2 hour enclosure...