Continue to Site

Eng-Tips is the largest engineering community on the Internet

Intelligent Work Forums for Engineering Professionals

  • Congratulations KootK on being selected by the Eng-Tips community for having the most helpful posts in the forums last week. Way to Go!

Search results for query: *

  1. TestMonkey

    Single Pole, Molded Case Breaker Testing <600v

    Yes it is cheaper to replace than test. But the circuit breakers that are found not to trip would be my concern. Having tested thousands of these small circuit breakers it is interesting on the number that just simply fail to trip (thermal or magnetic). In my experience, the failures seem to...
  2. TestMonkey

    Yanking a transfer switch.

    IEM, in Fremont, CA, can build a custom enclosure. They can also supply you with custom busbars, if needed. Plus it is local to you if you are indeed based out of Santa Cruz.
  3. TestMonkey

    Connecting 240mm2 cable to 160A circuit breaker

    Pin terminals. Several manufacturers are producing these.
  4. TestMonkey

    Testing Molded Case Breakers with Current Injection

    It is possible that the current standards no longer recommend the sizes for testing. I have seen older NFPA 70B documents stating 400A and above, but that looks to have been removed from the current version. By not recommending a size to test, the standard writers distance themselves should a...
  5. TestMonkey

    33/3.3kv transformer spurious trips

    Yes. It "could be" CT polarity is typically critical for REF protection. The polarity would be a good place to start your investigation.
  6. TestMonkey

    How to calculate CT ratio

    Transformer Turns Ratio (TTR) test
  7. TestMonkey

    Solid Earthed Neutral of Delta Wye(Star) Transformer

    Neutral to ground bonding can effect the proper functioning of ground fault protection schemes. Improper placement can create objectionable current or bypass the protection CT's. Also you may require an additional neutral to case bond for the transformer. A good review of NEC Article 250 could...
  8. TestMonkey

    2 MVA transformer Excitation Current Issue

    Thanks for the update. Hopefully you or the owner can reject the unit. Or the supplier does the right thing and replaces it without question.
  9. TestMonkey

    2 MVA transformer Excitation Current Issue

    Forgot to mention, typically during the Doble excitation test the measurements will be in mA and Watts. But every situation is different. The factory results are not to be considered for comparison, there is a published whitepaper dealing with that. Look for a copy of Doble Test Procedures...
  10. TestMonkey

    2 MVA transformer Excitation Current Issue

    Something is not right. Usually when it is me testing and I get results like that, I probably did something wrong. Connections or wrong programming of test equipment. Tested following standard Doble procedures? Forgive me for assuming the test set used was Doble M4000. Post indicates tested at...

Part and Inventory Search