Eng-Tips is the largest engineering community on the Internet

Intelligent Work Forums for Engineering Professionals

Search results for query: *

  1. beyond86

    Overvoltage During Earth Fault

    Kiribanda, 643А is not charging current, it's current which flow through neutral of ZNyn1 transformer. If you look at parameters you will see that this TR provide Io current 1000A during EF. 33 kV side works with low resistance neutral. 1) Is the 33kV system a real "DELTA" system? Yes. 2)...
  2. beyond86

    Overvoltage During Earth Fault

    Kiribanda, yes, you completely right, it's delta connection, but if you be more attentive, you will see transformer ZNyn1 at 33 kV side.
  3. beyond86

    Overvoltage During Earth Fault

    Kiribanda, look at 36 kV side, there is EF condition.
  4. beyond86

    Overvoltage During Earth Fault

    I was wrong about overvoltage at LV side of transformer ZNyn1. I built simple model of your SLD and got these results: Nothing happens with phase voltage at LV side. Can you please provide more details about what happens at LV side during EF condition (records)?
  5. beyond86

    Overvoltage During Earth Fault

    Actually, this is not typical solution for supply auxiliary. You will have overvolatge all time during EF condition because of transformer ZNyn1.
  6. beyond86

    Loop test of transformer 10/0.4 kV YYn0.

    Hi! I have one question. We have ungrounded 10 kV network. Transfromer 10/0.4 kV YYn0 connected to this network. 0.4 kV side of TR is solid grounded. Question: If I perform loop test at 0.4 kV side, I will see real earth fault current? For example I check it by Megger LTW425.
  7. beyond86

    Short circuit rating of substation equiments

    You have to limit short current to 31.5 kA for existing substation. How is old SS and new SS connect? Install series reactors at interconnection lines will help to limit SC for old SS.
  8. beyond86

    Transient stability in digsilent

    In this case, sym9910_1 has less rotor angel therefore out of step condition didn't happen. I think this generator works with close critical rotor angel and even short disturbance lead to out of step. Try to reduce active power for this generator and look at result.
  9. beyond86

    Transient stability in digsilent

    Misunderstood you. Try to reduce time to 20-30 ms. Initial rotor angle for sym9910_1 is close to critical, so in this case it will be difficult to keep stability under SC.
  10. beyond86

    Transient stability in digsilent

    1 sec is too long for such rotor angle.
  11. beyond86

    Transient stability in digsilent

    Yes, it's unstable. You have out of step condition for sym9910_1. Try to reduce clearing time of protection.
  12. beyond86

    Cross Tie Feeders - Interlocks & Protections

    Cross tie feeder is normally closed, isn't?
  13. beyond86

    Motor contribution current from LV motors.

    7anoter4, thanks for good explanation!
  14. beyond86

    Motor contribution current from LV motors.

    Additional question: There will be contribution current from LCI converter (load-commutated inverter 24 MW) which feed synchronous motor?
  15. beyond86

    Motor contribution current from LV motors.

    Additional info: I calculate SC at 110 kV bus, many LV motors 0.4 kv connected to transformers of 10/0.4 kV, then transformers 35/10 kV and then 110/35 transformers. Group of LV motors 0.4 kV => transformers 10/0.4 kV => transformers 35/10 kV => transformer 110/35 kV.
  16. beyond86

    Motor contribution current from LV motors.

    Hi! When we perform SC calculation, should taking into account motor contribution current from LV motors (0.4 kV or less) or only from MV motors? In which standard I can find information about this? Thanks in advance.
  17. beyond86

    motor starting calculation diverged

    Do you use motor acceleration or transient stability case? Check again motor paraments like CKT model, characteristic model, load model, inertia.
  18. beyond86

    Generator Control Panel and the Incoming - Protection functions

    Typically for 10 kV generator side we use follow protection: 50,51,59,27,32,40,46,81H/L,50N,69R,51V,87G. For 10 kV incomer side: 67, 67N (direction in generator)
Back
Top