I did search the internet and haven't found a calculation that I am confident with. In Sprinkler Design we use Hazen-Williams or occasionally...
The header pressure is set to meet the demand of the sprinkler system via a fire pump and jockey pump. The only issue is restricting the pressure directly as the 1 1/2" hose valve to a maximum of 100 PSI and a minimum of 65psi. Today this is done using a pressure restricting hose valve with...
Hi everyone,
This is a fire protection question relating to NFPA 14 however, the fluid dynamics remain the same. There is code in NFPA 14 that limits the residual pressure at any 1 1/2" fire hose to 100 psi. In the old days, restricted orifices would be installed after the 1 1/2" hose valve...
Hi everyone,
First of all, I am aware that restricted orifice inserts are not the recommended method for maintaining residual pressure below 100 psi in 1 1/2" hoses. However, a friend of mine is the Fire Technician at a hospital with over 700 of these restricted orifices installed. During a...