Thank you for the reply.
The motors are actually connected in parallel
The run boost setting is at 8
We actually found the problem which was on one of the isolators which had water in the junction box. The isolator was blown. Once we replaced the isolator. The reading is now at 1.3A
Thank...
Hi
Can anyone advise?
I have 2 motors which is rated at 0,75 kw each and 3 amp connected in series and a power flex 40 with a 6 amp max current rating.
The current limit setting on the drive is 6A.
The problem that I am experiencing is when the motor starts up to 70% it tripped with an F12...