  1. AHSEN_MEP

    Generator 400v step up to 11kv vector group confirmation

    Thank you for response @Che12345 Refer to my below message and your response , Please advise the number of ground rod and size , thank you 1. Neutral of Genset will be grounded . 20mm copper 3 mtrs rod is enough for Grounding ? Conductor size between neutral of Genset and Grounding rod ...
  2. AHSEN_MEP

    Generator 400v step up to 11kv vector group confirmation

    Dear Che12345 & xnuke Thank you for your response . From your relies followings are clarified : 1. Step up transformer .4/11kv yNd11 that LV side is Delta and MV side is star and solidly grounded 2.Gensets neutral will be soldily grounded 3.There is no requirement of Neutral bus bar in...
  3. AHSEN_MEP

    Generator 400v step up to 11kv vector group confirmation

    We have 1250kva two generators of CAT which is giving output of 400voltage . These genset will be connected to synchronizing panel. After Sync Panel we will connect it with 2500KVA step up transformer .4/11kv . This transformer will convert voltage into 11kv . vector group of this transformer...
  4. AHSEN_MEP

    Generator 400v output to 11kv step up transformer - need vector group confirmation

    thank you for ur support , We will ground the neutral of generators , 2 x earth pits with 20mm x 3mtrs copper rod with grounding enhancement furse - cement for each generator Neutral . Generator body will be seperately grounded through seperate earth pit .will it ne enough . please guide ...
  5. AHSEN_MEP

    Generator 400v output to 11kv step up transformer - need vector group confirmation

    We have 1250kva two generators of CAT which is giving output of 400voltage . These genset will be connected to synchronizing panel. After Sync Panel we will connect it with 2500KVA step up transformer .4/11kv . This transformer will convert voltage into 11kv . vector group of this transformer...