So, overall, would you consider pipe manufactured to ASTM A312 to be superior to A778. I am tabulating some of the differences as follows, based on what I have found:
• A312 is commonly used higher temp and higher pressure applications such as steam boilers, pressure vessels, etc.
• A312 has...
Generally speaking, does ASTM A312 or A778 provide better protection against corrosion. I have no specific application, but just trying to determine the main differences between the two standards for 304L/316L SS piping as related to corrosion.
Yeah, I am definitely replacing it. In fact, I have the new one in the back of my car and will replace this evening, but just wondering if you guys have ever heard of anything like this happen. It is not on a GFCI, but it is not in a wet location either. I installed the one being replaced in...
Hoping one of you electrical guys can offer a possible answer to this:
I have a 9 yr old 1500W baseboard heater in one of my rooms. As I was walking by this morning, a loud pop and flash came from the middle of the heater (not at the junction box). Upon inspecting it, there was black residue...
Having a debate with colleagues whether there is a difference between these two types of pneumatic actuated valves. Can't find a clear definition which would explain the difference, but don't all pneumatic valves have electric solenoids (AC or DC) to control the air flow to the valves cylinder...
I am working on a plant in NY that requires 93% sulfuric acid, so part of the plant is the design of the tanker truck unloading station to fill a 6000 gallon tank that will be located in an adjacent building. Can anyone point me in the right direction for codes and requirements for the...
Good point guys! The water rise is likely more due to oscillation during shut down as opposed to the vacuum created from the pipe cooling. I'm having them adjust the ramp down time on the blower to try to minimize this effect. They do have manual drains at the low point of the piping.
Attached is a diagram of the existing system. I'm recommending a siphon break at the high point of the piping at the top of the tank, but this is an inaccessible location, so the client has suggested locating it inside the building right after the blower discharge. I certainly prefer it being...
We have a client with an aeration system that consists of a 32' tall aeration tank with approx. 28' of liquid. The PD blowers are in a nearby building at ground level. The piping goes up and over the wall of the aeration tank to the bottom of the tank where the aeration diffusers are. When...
Thanks LittleInch, but I think you're mixing my flow and pressure numbers. The flow is 60 gpm and 50 gpm, so 110 gpm was what I was suggesting as a flow requirement but I would suggest a bit more as a safety factor. Likewise for the pressure, I would tell them a bit higher as an allowance for...
We have two pieces of equipment that requires process water in a new building. One requires 60 gpm @ 70 psi and the other requires 50 gpm @ 65 psi and will operate concurrently. We want to advise the owner of the total flow/pressure required coming into the building. Is this simply the...
Static Readings:
Suction: 4.5 psi on both pumps (This seems to be close to what the suction head of the tank is)
Discharge: 4 psi on one pump gauge and 3 psi on the other
So, when the pumps are turned on, the suction gauges go to 4 psi and the discharge gauges go to 2 psi.
Yeah, that's what I'm thinking as well. Other thoughts is actually a broken shaft, but that would be highly unusual, especially in both pumps. Wouldn't a blockage in the suction cause an increase in amps though?
We are starting up a system and apparently getting no flow from the pump and no increase in discharge pressure and low amps. I'm thinking the rotation may be reversed. I originally thought a blocked/closed suction, but upon checking the amps, I'm leaning towards a rotational issue?